TECHNICAL SPECIFICATIONS
Aerial bundled cable cross section |
Branch cable cross section |
Conductor type of connectable cable |
Tightening torque of bolt |
16-70 mm2 |
1.5-10 mm2 |
Aluminum-Copper |
9±1 Nm |
PARTS AND COMPONENTS
Exterior body (main): including two parts of the base and the insulated upper shell made of UV and weather resistant fiber reinforced polyamide materials.
Conductive metal (Teeth): Plated conductive metal alloy (Other metal alloy and plating types are available upon request)
Sealing gasket: UV and weather resistant rubber materials impregnated with moisture resistant grease
Bolt: M8 Galvanized steel bolt
Nut and washer: Galvanized steel
INSTALLATION METHOD
First, unscrew the connector screw and separate the base and the insulated upper shell. Place the aerial bundled cable on the teeth. Insert the branch conductor wire from the desired side through the insulated upper shell up to the end of the cable end cap. Then place the insulated upper shell on the base and fasten the screws to fully connect the connector to the branch conductor wire. To prevent rotating the connector while tightening the bolt, 18 mm boxing wrench can be used in boxing.
PACKAGING
120 PCS/CTN